Wire size

Wire size for 70 amps

A 70 amp circuit needs 4 AWG copper at the 75 degree C column of NEC Table 310.16, or 3 AWG aluminium. If the terminations are only rated 60 degrees C, which is common on equipment at 100 amps or less, you need 4 AWG copper instead.

Conductor size for 70 amps

Copper, 75 °C 4AWG
Copper, 60 °C 4AWG
Aluminium, 75 °C 3AWG
Breaker 70A

NEC 110.14(C) limits you to the lowest-rated termination in the circuit, which on most equipment at 100 amps or less is 60 °C. Check the breaker and the device before using the 75 °C column.

Minimum conductor for 70 A by material and insulation rating
Material60 °C75 °C90 °C
Copper446
Aluminium234
Voltage drop on 4 AWG copper at 240 V, single phase, the usual voltage for a 70 A circuit
One-way runDropPercentWithin 3%
50 ft 2.2 V 0.9% Yes
100 ft 4.3 V 1.8% Yes
150 ft 6.5 V 2.7% Yes
200 ft 8.7 V 3.6% No, size up

What runs on a 70 amp circuit

Subpanels, electric furnaces and larger workshop feeders.

The thing to watch on this circuit

Four AWG copper covers 70 A at 75 degrees C with margin, which is why 70 A circuits are often run in the same conductor as 85 A ones.

Common questions

What size wire do I need for 70 amps?

A 70 amp circuit needs 4 AWG copper at the 75 degree C column of NEC Table 310.16, or 3 AWG aluminium. If the terminations are only rated 60 degrees C, which is common on equipment at 100 amps or less, you need 4 AWG copper instead.

What breaker goes with a 70 amp circuit?

A 70 amp breaker. The conductor is sized to the breaker, not the other way round, and NEC 240.4 requires the overcurrent device to protect the conductor.

How far can I run 70 amps before voltage drop matters?

On 4 AWG copper at 240 volts, voltage drop reaches 0.9 percent at 50 feet and 3.6 percent at 200 feet. The NEC recommends staying under 3 percent on a branch circuit in the informational note to 210.19(A)(1), which is advice rather than a requirement, so beyond about 200 feet you should go up a size.

Can I use aluminium wire for a 70 amp circuit?

Yes, at 3 AWG for the 75 degree C column, which is larger than the copper equivalent. Aluminium is common and cost-effective on feeders and services, but the terminations must be listed for aluminium and an antioxidant compound is normally required.

What is a 70 amp circuit usually for?

Subpanels, electric furnaces and larger workshop feeders.

Conductor sizes are computed from NEC Table 310.16 with the 240.4(D) small-conductor cap applied. Table 310.16 assumes not more than three current-carrying conductors at 30 °C ambient; correct for ambient (310.15(B)(1)) and conductor count (310.15(C)(1)) before use, and verify against the code edition your jurisdiction has adopted.