Wire size

Wire size for 100 amps

A 100 amp circuit needs 3 AWG copper at the 75 degree C column of NEC Table 310.16, or 1 AWG aluminium. If the terminations are only rated 60 degrees C, which is common on equipment at 100 amps or less, you need 1 AWG copper instead.

Conductor size for 100 amps

Copper, 75 °C 3AWG
Copper, 60 °C 1AWG
Aluminium, 75 °C 1AWG
Breaker 100A

NEC 110.14(C) limits you to the lowest-rated termination in the circuit, which on most equipment at 100 amps or less is 60 °C. Check the breaker and the device before using the 75 °C column.

Minimum conductor for 100 A by material and insulation rating
Material60 °C75 °C90 °C
Copper133
Aluminium1/012
Voltage drop on 3 AWG copper at 240 V, single phase, the usual voltage for a 100 A circuit
One-way runDropPercentWithin 3%
50 ft 2.5 V 1.0% Yes
100 ft 4.9 V 2.0% Yes
150 ft 7.4 V 3.1% No, size up
200 ft 9.8 V 4.1% No, size up

What runs on a 100 amp circuit

Subpanels, detached garages and workshops, small dwelling services and larger HVAC equipment.

The thing to watch on this circuit

Most 100 A panels and breakers carry 75 degree C terminations, but check: a 60 degree C rating forces the 60 degree column and pushes you from 3 AWG copper to 1 AWG.

Common questions

What size wire do I need for 100 amps?

A 100 amp circuit needs 3 AWG copper at the 75 degree C column of NEC Table 310.16, or 1 AWG aluminium. If the terminations are only rated 60 degrees C, which is common on equipment at 100 amps or less, you need 1 AWG copper instead.

What breaker goes with a 100 amp circuit?

A 100 amp breaker. The conductor is sized to the breaker, not the other way round, and NEC 240.4 requires the overcurrent device to protect the conductor.

How far can I run 100 amps before voltage drop matters?

On 3 AWG copper at 240 volts, voltage drop reaches 1.0 percent at 50 feet and 4.1 percent at 200 feet. The NEC recommends staying under 3 percent on a branch circuit in the informational note to 210.19(A)(1), which is advice rather than a requirement, so beyond about 150 feet you should go up a size.

Can I use aluminium wire for a 100 amp circuit?

Yes, at 1 AWG for the 75 degree C column, which is larger than the copper equivalent. Aluminium is common and cost-effective on feeders and services, but the terminations must be listed for aluminium and an antioxidant compound is normally required.

What is a 100 amp circuit usually for?

Subpanels, detached garages and workshops, small dwelling services and larger HVAC equipment.

Conductor sizes are computed from NEC Table 310.16 with the 240.4(D) small-conductor cap applied. Table 310.16 assumes not more than three current-carrying conductors at 30 °C ambient; correct for ambient (310.15(B)(1)) and conductor count (310.15(C)(1)) before use, and verify against the code edition your jurisdiction has adopted.