Wire size

Wire size for 40 amps

A 40 amp circuit needs 8 AWG copper at the 75 degree C column of NEC Table 310.16, or 8 AWG aluminium. If the terminations are only rated 60 degrees C, which is common on equipment at 100 amps or less, you need 8 AWG copper instead.

Conductor size for 40 amps

Copper, 75 °C 8AWG
Copper, 60 °C 8AWG
Aluminium, 75 °C 8AWG
Breaker 40A

NEC 110.14(C) limits you to the lowest-rated termination in the circuit, which on most equipment at 100 amps or less is 60 °C. Check the breaker and the device before using the 75 °C column.

Minimum conductor for 40 A by material and insulation rating
Material60 °C75 °C90 °C
Copper888
Aluminium688
Voltage drop on 8 AWG copper at 240 V, single phase, the usual voltage for a 40 A circuit
One-way runDropPercentWithin 3%
50 ft 3.1 V 1.3% Yes
100 ft 6.3 V 2.6% Yes
150 ft 9.4 V 3.9% No, size up
200 ft 12.5 V 5.2% No, size up

What runs on a 40 amp circuit

Electric ranges in smaller kitchens, large water heaters, and Level 2 EV chargers rated 32 A continuous.

The thing to watch on this circuit

Eight AWG copper is 40 A only in the 60 degree column and 50 A at 75 degrees, so the termination rating decides whether 8 AWG is comfortable or marginal here.

Common questions

What size wire do I need for 40 amps?

A 40 amp circuit needs 8 AWG copper at the 75 degree C column of NEC Table 310.16, or 8 AWG aluminium. If the terminations are only rated 60 degrees C, which is common on equipment at 100 amps or less, you need 8 AWG copper instead.

What breaker goes with a 40 amp circuit?

A 40 amp breaker. The conductor is sized to the breaker, not the other way round, and NEC 240.4 requires the overcurrent device to protect the conductor.

How far can I run 40 amps before voltage drop matters?

On 8 AWG copper at 240 volts, voltage drop reaches 1.3 percent at 50 feet and 5.2 percent at 200 feet. The NEC recommends staying under 3 percent on a branch circuit in the informational note to 210.19(A)(1), which is advice rather than a requirement, so beyond about 150 feet you should go up a size.

Can I use aluminium wire for a 40 amp circuit?

Yes, at 8 AWG for the 75 degree C column, which is the same size than the copper equivalent. Aluminium is common and cost-effective on feeders and services, but the terminations must be listed for aluminium and an antioxidant compound is normally required.

What is a 40 amp circuit usually for?

Electric ranges in smaller kitchens, large water heaters, and Level 2 EV chargers rated 32 A continuous.

Conductor sizes are computed from NEC Table 310.16 with the 240.4(D) small-conductor cap applied. Table 310.16 assumes not more than three current-carrying conductors at 30 °C ambient; correct for ambient (310.15(B)(1)) and conductor count (310.15(C)(1)) before use, and verify against the code edition your jurisdiction has adopted.