Wire size

Wire size for 200 amps

A 200 amp circuit needs 3/0 AWG copper at the 75 degree C column of NEC Table 310.16, or a larger aluminium conductor. If the terminations are only rated 60 degrees C, which is common on equipment at 100 amps or less, you need a larger conductor copper instead.

Conductor size for 200 amps

Copper, 75 °C 3/0AWG
Copper, 60 °C AWG
Aluminium, 75 °C AWG
Breaker 200A

NEC 110.14(C) limits you to the lowest-rated termination in the circuit, which on most equipment at 100 amps or less is 60 °C. Check the breaker and the device before using the 75 °C column.

Minimum conductor for 200 A by material and insulation rating
Material60 °C75 °C90 °C
Copper3/03/0
Aluminium4/0
Voltage drop on 3/0 AWG copper at 240 V, single phase, the usual voltage for a 200 A circuit
One-way runDropPercentWithin 3%
50 ft 1.5 V 0.6% Yes
100 ft 3.1 V 1.3% Yes
150 ft 4.6 V 1.9% Yes
200 ft 6.2 V 2.6% Yes

What runs on a 200 amp circuit

Standard modern dwelling service, large subpanels and shop services.

The thing to watch on this circuit

Two hundred amp services are commonly run in 2/0 copper or 4/0 aluminium. Service entrance conductors may use NEC 310.12 dwelling ratios, which permit smaller conductors than Table 310.16 alone.

Common questions

What size wire do I need for 200 amps?

A 200 amp circuit needs 3/0 AWG copper at the 75 degree C column of NEC Table 310.16, or a larger aluminium conductor. If the terminations are only rated 60 degrees C, which is common on equipment at 100 amps or less, you need a larger conductor copper instead.

What breaker goes with a 200 amp circuit?

A 200 amp breaker. The conductor is sized to the breaker, not the other way round, and NEC 240.4 requires the overcurrent device to protect the conductor.

How far can I run 200 amps before voltage drop matters?

On 3/0 AWG copper at 240 volts, voltage drop reaches 0.6 percent at 50 feet and 2.6 percent at 200 feet. The NEC recommends staying under 3 percent on a branch circuit in the informational note to 210.19(A)(1), which is advice rather than a requirement, so this conductor stays inside 3 percent for all of these distances.

Can I use aluminium wire for a 200 amp circuit?

Table 310.16 does not list an aluminium conductor small enough for this circuit, so use copper.

What is a 200 amp circuit usually for?

Standard modern dwelling service, large subpanels and shop services.

Conductor sizes are computed from NEC Table 310.16 with the 240.4(D) small-conductor cap applied. Table 310.16 assumes not more than three current-carrying conductors at 30 °C ambient; correct for ambient (310.15(B)(1)) and conductor count (310.15(C)(1)) before use, and verify against the code edition your jurisdiction has adopted.