Wire size

Wire size for 60 amps

A 60 amp circuit needs 6 AWG copper at the 75 degree C column of NEC Table 310.16, or 4 AWG aluminium. If the terminations are only rated 60 degrees C, which is common on equipment at 100 amps or less, you need 4 AWG copper instead.

Conductor size for 60 amps

Copper, 75 °C 6AWG
Copper, 60 °C 4AWG
Aluminium, 75 °C 4AWG
Breaker 60A

NEC 110.14(C) limits you to the lowest-rated termination in the circuit, which on most equipment at 100 amps or less is 60 °C. Check the breaker and the device before using the 75 °C column.

Minimum conductor for 60 A by material and insulation rating
Material60 °C75 °C90 °C
Copper466
Aluminium344
Voltage drop on 6 AWG copper at 240 V, single phase, the usual voltage for a 60 A circuit
One-way runDropPercentWithin 3%
50 ft 2.9 V 1.2% Yes
100 ft 5.9 V 2.5% Yes
150 ft 8.8 V 3.7% No, size up
200 ft 11.8 V 4.9% No, size up

What runs on a 60 amp circuit

Small subpanels, electric furnaces, large air conditioners and workshop feeders.

The thing to watch on this circuit

Sixty amps is the point where aluminium starts to make economic sense on longer runs, at 4 AWG against 6 AWG copper.

Common questions

What size wire do I need for 60 amps?

A 60 amp circuit needs 6 AWG copper at the 75 degree C column of NEC Table 310.16, or 4 AWG aluminium. If the terminations are only rated 60 degrees C, which is common on equipment at 100 amps or less, you need 4 AWG copper instead.

What breaker goes with a 60 amp circuit?

A 60 amp breaker. The conductor is sized to the breaker, not the other way round, and NEC 240.4 requires the overcurrent device to protect the conductor.

How far can I run 60 amps before voltage drop matters?

On 6 AWG copper at 240 volts, voltage drop reaches 1.2 percent at 50 feet and 4.9 percent at 200 feet. The NEC recommends staying under 3 percent on a branch circuit in the informational note to 210.19(A)(1), which is advice rather than a requirement, so beyond about 150 feet you should go up a size.

Can I use aluminium wire for a 60 amp circuit?

Yes, at 4 AWG for the 75 degree C column, which is larger than the copper equivalent. Aluminium is common and cost-effective on feeders and services, but the terminations must be listed for aluminium and an antioxidant compound is normally required.

What is a 60 amp circuit usually for?

Small subpanels, electric furnaces, large air conditioners and workshop feeders.

Conductor sizes are computed from NEC Table 310.16 with the 240.4(D) small-conductor cap applied. Table 310.16 assumes not more than three current-carrying conductors at 30 °C ambient; correct for ambient (310.15(B)(1)) and conductor count (310.15(C)(1)) before use, and verify against the code edition your jurisdiction has adopted.