Wire size

Wire size for 50 amps

A 50 amp circuit needs 8 AWG copper at the 75 degree C column of NEC Table 310.16, or 6 AWG aluminium. If the terminations are only rated 60 degrees C, which is common on equipment at 100 amps or less, you need 6 AWG copper instead.

Conductor size for 50 amps

Copper, 75 °C 8AWG
Copper, 60 °C 6AWG
Aluminium, 75 °C 6AWG
Breaker 50A

NEC 110.14(C) limits you to the lowest-rated termination in the circuit, which on most equipment at 100 amps or less is 60 °C. Check the breaker and the device before using the 75 °C column.

Minimum conductor for 50 A by material and insulation rating
Material60 °C75 °C90 °C
Copper688
Aluminium466
Voltage drop on 8 AWG copper at 240 V, single phase, the usual voltage for a 50 A circuit
One-way runDropPercentWithin 3%
50 ft 3.9 V 1.6% Yes
100 ft 7.8 V 3.3% No, size up
150 ft 11.7 V 4.9% No, size up
200 ft 15.6 V 6.5% No, size up

What runs on a 50 amp circuit

Electric ranges and cooktops, RV shore power, welders, hot tubs and Level 2 EV chargers rated at 40 A continuous.

The thing to watch on this circuit

A 50 A circuit feeding a continuous load, which includes an EV charger, must be sized at 125 percent of that load under NEC 210.19(A)(1), so a 40 A continuous charger is exactly what a 50 A circuit is for.

Common questions

What size wire do I need for 50 amps?

A 50 amp circuit needs 8 AWG copper at the 75 degree C column of NEC Table 310.16, or 6 AWG aluminium. If the terminations are only rated 60 degrees C, which is common on equipment at 100 amps or less, you need 6 AWG copper instead.

What breaker goes with a 50 amp circuit?

A 50 amp breaker. The conductor is sized to the breaker, not the other way round, and NEC 240.4 requires the overcurrent device to protect the conductor.

How far can I run 50 amps before voltage drop matters?

On 8 AWG copper at 240 volts, voltage drop reaches 1.6 percent at 50 feet and 6.5 percent at 200 feet. The NEC recommends staying under 3 percent on a branch circuit in the informational note to 210.19(A)(1), which is advice rather than a requirement, so beyond about 100 feet you should go up a size.

Can I use aluminium wire for a 50 amp circuit?

Yes, at 6 AWG for the 75 degree C column, which is larger than the copper equivalent. Aluminium is common and cost-effective on feeders and services, but the terminations must be listed for aluminium and an antioxidant compound is normally required.

What is a 50 amp circuit usually for?

Electric ranges and cooktops, RV shore power, welders, hot tubs and Level 2 EV chargers rated at 40 A continuous.

Conductor sizes are computed from NEC Table 310.16 with the 240.4(D) small-conductor cap applied. Table 310.16 assumes not more than three current-carrying conductors at 30 °C ambient; correct for ambient (310.15(B)(1)) and conductor count (310.15(C)(1)) before use, and verify against the code edition your jurisdiction has adopted.